通信局(站)低压配电系统用电涌保护器检验实施细则目录1编制依据及适用范围····························································································12引用标准··················································································································13检验项目及技术要求·····························································································
13.1检验项目及技术要求·····················································································
13.2对各种类型SPD检测项目·········································································74检验方法··················································································································95抽样·························································································································
95.1抽样基数·········································································································
95.2样品数量·········································································································96质量判定·················································································································
96.1通信局(站)低压配电系统用电涌保护器监督总体的检验项目和质量判定·····················································································································
96.2判定准则··········································································································9通信局(站)低压配电系统用电涌保护器检验实施细则1编制依据及适用范围本实施细则依据YD/T
1235.1-2002《通信局(站)低压配电系统用电涌保护器技术要求》编制本细则适用于通信局(站)低压配电系统用电涌保护器的质量检验2引用标准GB/T4942-1993低压电器外壳防护等级(eqvIEC60947:1988)YD/T
1235.2-2002通信局(站)低压配电系统用电涌保护器测试方法3检验项目及技术要求
3.1检验项目及技术要求(见表1至表10)表1检验项目及技术要求序号项目名称技术要求1外观质量a电涌保护器表面应平整、光洁、无划伤、无裂痕及变形,紧固件应牢固,颜色应均匀无明显差异b标志应完整清晰、耐久可靠,内容完全,且铭牌不应出现移动和任何翘曲现象2保护模式交流SPD必须具备N-PE、L-PE或L-N-PE的保护模式;直流SPD必须具备V+-V-的保护模式交流SPD宜具备L-N的保护模式;直流SPD宜具备V+-PE或V--PE的保护模式3分离装置SPD在故障或失效时,应有与电源系统永久断开的分离装置4告警功能SPD正常或故障时,应有能正确表示其状态的标志或指示灯SPD宜具备远程集中监测或集中告警的接口5接线端子连接导体的能力SPD的接线端子除应符合GB17464的要求外,其连接导线的能力还应符合表2或表3的要求6最大持续运行电压在70±3℃的试验环境下,施加规定的Uc持续48h,SPD应满足下列要求a)试验过程中,SPD应能稳定地正常工作、没有可见可闻的损坏;b)试验前后的限制电压和点火电压应小于UP,且限制电压的变化率不应大于±5%;c)试验过程中,SPD的分离装置不应动作7电压保护水平SPD的电压保护水平UP应符合制造商所规定的数值8等级限制电压施加表4规定的等级测试电流IB时,限压特性的SPD的等级限制电压UB应符合表4的要求9动作负载试验在最大持续运行电压Uc下,SPD应能耐受规定波形、幅值和次数的冲击电流而不发生实质性损坏SPD的雷击动作负载试验通过的判据如下a)在预备性试验和动作负载试验期间的每次冲击后,SPD都应能满足热平衡的要求;b)SPD应能自行遮断试验中产生的任何续流;c)试验中SPD应不出现击穿、闪络或机械损伤等现象;d)试验前后的限制电压和点火电压均应小于UP;e)试验中SPD的告警或分离装置不应动作10电气间隙和爬电距离电气间隙和爬电距离应符合表5的要求11外壳防护等级SPD的外壳防护等级(IP代码)应符合GB
4942.2中规定的IP2LX12保护接地a)SPD在按正常使用条件安装和连接时,其非带电的易触及的金属部件(用于固定基座、罩盖、铆钉、铭牌等以及与带电部件绝缘的小螺钉除外)应连接成一个整体后与保护接地端子可靠连接;b)保护接地端子螺钉的尺寸应不小于M4;c)保护接地应采用符合国标的标记加以识别,如字母标记PE,图形符号〨等13着火危险性(灼热丝试验)SPD的绝缘部件必须有足够的阻燃能力绝缘部件在进行表6规定的灼热丝试验时,试品在下列情况可看作通过了试验——没有可见的火焰或持续火光;——灼热丝移开后,试品上的火焰或火光在30s内自行熄灭,并且不应点燃试验用的铺底层中的薄绵纸(绢纸)、或烧焦松木板14暂时过电压失效安全性安装在L-PE或N-PE之间的SPD,在施加表7规定的异常的暂时过电压UT条件下,SPD故障时应具有安全的失效模式,试验期间不能点燃薄绵纸或粗绵布15暂时过电压耐受特性安装在L-PE或L-N之间的SPD应能耐受表8规定的暂态过电压UT,并满足如下技术要求a)UT断开后,SPD在Uc下应能达到热平衡;(注如果在施加Uc的最后15min内,SPD的功耗或温度或流过SPD的阻性电流分量能稳定地降低,则认为SPD达到热平衡)b)试验后SPD的限制电压和点火电压均应小于UP;c)SPD的辅助电路,如状态指示灯应能正常地工作;注电涌保护电路以外的其它电路称为辅助电路d)SPD没有出现任何损坏的迹象16热稳定性按表9规定的每一试验电流等级进行的热稳定性试验时,SPD应满足如下要求a)SPD持续通过每一档试验电流等级时,都应能达到热平衡或使其分离装置动作;注当电流持续通过SPD时,10min内其温度的增加值小于2℃,则认为达到热平衡b)在试验期间,SPD的表面温度应始终低于120℃;分离装置动作后在5min内,SPD的表面温度应低于80℃c)如果SPD的分离装置动作,则对应SPD施加2Uc的工频电压,持续1min,此时应无超过
0.5mAr.m.s的电流流过SPD17电压降a)二端口交流SPD的L-N之间通过电阻性的额定负载电流IR时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降应不大于2%b)二端口直流SPD的V+-V-之间通过电阻性的额定负载电流IR时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降,应不大于
0.5%18负载侧电涌耐受能力二端口SPD的负载侧应能承受制造商规定的电涌电流的冲击19负载侧短路耐受能力在负载短路的条件下,二端口SPD应能承载制造商规定的短路电流预期短路电流和功率因数应根据表10给出试验结果的合格判据如下a)试验过程中,短路电流应在5s中断开,薄绵纸或粗绵布应不着火此外,不应有爆炸或对人身或设施的其它危害发生b)如果分离装置动作,则对应SPD施加2Uc的工频电压,持续1min,此时应无超过
0.5mAr.m.s的电流流过SPD注17,18,19项不适用一端口SPD表2一端口SPD接线端子允许连接铜导线的标称截面积SPD类型能被夹紧的导线标称截面尺寸mm2交流SPDT型H型M型L型25~5016~3510~254~16直流SPDH型L型4~
162.5~6表3二端口SPD接线端子允许连接铜导线的标称截面积额定负载电流IRA能被夹紧的导线标称截面尺寸mm2IR≤1313IR≤1616IR≤2525IR≤3232IR≤5050IR≤8080IR≤100100IR≤1251~
2.51~
41.5~
62.5~104~1610~2516~3525~50注1对于额定负载电流小于或等于50A的SPD,要求接线端子的结构能紧固实心导体以及硬性多股绞合导体,允许使用软导体2二端口SPD接线端子连接导线的能力除应符合本表的要求外,还应根据其标称放电电流的大小,同时符合表3的要求表4限压特性的SPD的等级限制电压UB最大持续运行电压Uc交流SPD的UB上限值(V)直流SPD的UB上限值(V)T型IB=60kAH型IB=40kAM型L型IB=5kAH型IB=5kAL型IB=2kAIB=25kAIB=15kA45V—————42525052V—————45027575V—————50032585V—————550350275V2600210016001250950——320V28502300170014501150——385V32002600200018001400——420V34502800220019001600——460V37003000250021001750——510V39503200270023001900——600V44003600310027002300——表5电气间隙和爬电距离检查部位1)接线端子不同相的带电导体之间2)接线端子各相与接地端子、零线端子之间;固定SPD的金属螺钉、外壳、机箱、面盖或其它金属工件之间SPD的Uc100V100~200V200~450V450~600V电气间隙和爬电距离(mm)≥2≥4≥6≥11表6SPD绝缘材料的灼热丝试验条件试验绝缘零件灼热丝顶端温度℃试验持续时间s支持或固定接线端子各相载流部件和保护电路部件的外部绝缘零件850±1530±1不支持或固定载流部件的绝缘外壳、其它外部绝缘零件650±1030±1注1就本试验而言,平面安装式SPD的机座可看作为外部零件2对陶瓷材料制成的部件不进行本试验3如果绝缘零件是由同一种材料制成,则仅对其中一个零件按相应的灼热丝试验温度进行本试验表7TOV失效安全性试验条件保护模式暂时过电压Vr.m.s试验持续时间sL-PE、N-PE12005表8TOV耐受特性条件保护模式暂时过电压UTVr.m.s试验持续时间minL-PE380120L-N320120表9热稳定性试验电流等级序号123456试验电流等级mAr.m.s5000250010003208020表10预期短路电流(Ip)和功率因数(cos)Ip(kA)%cos()Ip≤
1.
50.
951.5Ip≤
3.
00.
93.0Ip≤
4.
50.
84.5Ip≤
6.
00.
76.0Ip≤
10.
00.
510.0Ip≤
20.
00.
320.0Ip≤
50.
00.
2550.0Ip
0.
23.2对各种类型SPD检测项目(见表11)表
11.通信局(站)低压配电系统用电涌保护器测试项目低压配电系统用电涌保护器产品名称检测项目名称一端口单相交流浪涌保护器二端口单相交流浪涌保护器一端口三相交流浪涌保护器二端口三相交流浪涌保护器一端口直流浪涌保护器二端口直流浪涌保护器1外观质量√√√√√√2保护模式√√√√√√3分离装置√√√√√√4告警功能√√√√√√5接线端子连接导体的能力√√√√√√6最大持续运行电压√√√√√√7电压保护水平√√√√√√8等级限制电压√√√√√√9动作负载试验√√√√√√10电气间隙和爬电距离√√√√√√表11(续).通信局(站)低压配电系统用电涌保护器测试项目低压配电系统用电涌保护器产品名称检测项目名称一端口单相交流浪涌保护器二端口单相交流浪涌保护器一端口三相交流浪涌保护器二端口三相交流浪涌保护器一端口直流浪涌保护器二端口直流浪涌保护器11外壳防护等级√√√√√√12保护接地√√√√√√13着火危险性(灼热丝试验)√√√√√√14暂时过电压失效安全性15暂时过电压耐受特性√√√√16热稳定性√√√√√√17电压降√√√18负载侧电涌耐受能力√√√19负载侧短路耐受能力必须检测项目数注表中打“√”的检测项目为该产品必须进行的检测项目,打“”的检测项目为该产品参考检测项目4检验方法检验方法参考YD/T
1235.2-2002《通信局(站)低压配电系统用电涌保护器测试方法》5抽样
5.1抽样基数——装配完整的电涌保护器整机(箱体)不少于8个;——结构相同的保护单元(模块)不少于25个
5.2样品数量——装配完整的电涌保护器整机2个;——结构相同的保护单元9个6质量判定
6.1通信局(站)低压配电系统用电涌保护器监督总体的检验项目和质量判定(见表12)
6.2判定准则产品出现1项B类不合格或多于2项C类不合格时,判该监督总体不合格表12质量判定序号项目名称不合格类别B类C类1外观质量O2保护模式O3分离装置O4告警功能O5接线端子连接导体的能力O6最大持续运行电压O7电压保护水平O8等级限制电压O9动作负载试验O10电气间隙和爬电距离O11外壳防护等级O12保护接地O13着火危险性(灼热丝试验)O14暂时过电压失效安全性(参考项)15暂时过电压耐受特性(直流浪涌保护器为参考项)O16热稳定性O17电压降O18负载侧电涌耐受能力O19负载侧短路耐受能力(参考项)。